Water treatment UV sterilizer:
1. Model number and flow rate: CR-60 (1GPM)
2. The Ultraviolet dosage is more than 40,000 Microwatt Seconds/cm2, according to NSF55 Class
A standard.
3. 304 stainless steel, polished and passivated.
4. Ballast: 10~16W, 220V/50Hz, with CE certificate. LED alarm, Dry contact, Overheating protection,
Instant start.
5. Lamp life: 9000-10000 hours of operation approx. 12 months of continuous service.
6. Maximum working pressure: 100 PSI
7. Recommended ambient temperature: 2-40 C (36-104 F)
8. General installation conditions and needs: Avoid touching the sides of the quartz sleeve and lamp,
handle by the ends only, Ultraviolet lamp and quartz sleeve are easily damaged.
9. General operation and maintenance: Quartz thimble is to be cleaned every 6-12 months, and to be replaced every 24 months. UV lamp is to be replaced every year.
Model | Flow Rate | Quartz Thimble Size | Standard Inlet & Outlet | UV lamps | Standard Ballast | |
GPM | LPH | mm | inch | |||
CR-60 | 1 | 226 | D24.5* 250 | 1/4 | T510 | UV-3(2B) |