Model: YD4UI-9X4
Technical parameter
Performance | Parameter | |||
Network | 3 phase 3 line,3 phase 4 line | |||
Voltage | Rated voltage | AC100V,400V(please note when purchase) | ||
Overload | Permanent:1.2 times temporary:2 times/10s | |||
Power consumption | <1VA(each phase) | |||
Impedance | >300kΩ | |||
Accuracy | RMS measurement, CLASS 0.5 | |||
Current | Rated current | AC1A,5A(please note when purchase) | ||
Over load | Permanent,:1.2 times temporary:2 times/10s | |||
Power consumption | <0.4VA(each phase) | |||
Impedance | <200KΩ | |||
Accuracy | RMS measurement, CLASS 0.2 | |||
Frequency | 40~60Hz, accuracy 0.2Hz | |||
Function | Active power, Reactive power, Apparent power, Accuracy: 0.5% class | |||
Electric energy | Four quadrant measurement, active poweraccuracy rate0.5 class, reactive power accuracy rate0.5% class | |||
Display | Programmable, switching, circular two, three, or four rows LED display | |||
Operation range | AC/DC 80~270V | |||
Power consumption | <5VA | |||
Digital interface | RS-485,MODBUS-RTU | |||
Pulse input | Two power pulse output, photo-couple relay | |||
Working environment | -10~55ºC | |||
Store environment | -20~75ºC | |||
Voltage withstand | Input and power>2kV, input andoutput>2kV, power and output>1kV | |||
Insulation | Input, output, power supply to machine hull >5M |
Panel description