Ads by Google
This cable is LV 0.6/1KV power cable. Cu/XLPE/PVC/SWA/PVC 3x4mm2 enclose below test report
Item no. | Test contents | Unit | Standard requirements | Results | Pass or not |
1 | Conductor structure | Nos.x mm | 1/2.25 | 1/2.25 | √ |
2 | Average thickness of insulation | mm | ≥0.7 | 0.8 | √ |
3 | Min thickness of insulation | mm | ≥ 0.53 | 0.62 | √ |
4 | Insulation spark test | KV | 6 | pass | √ |
5 | Average thickness of out sheath | mm | ≥1.8 | 1.9 | √ |
6 | Min thickness of out sheath | mm | ≥ 1.24 | 1.38 | √ |
7 | DC resistance of conductor | Ω/km(20 ) | ≤ 4.61 | 4.56 | √ |
8 | AC voltage test | 3.5KV/5min not spark through | pass | √ | |
Conclusion | This product is mached to GB/T12706-2002 |
Low Voltage Power Cable 3x4mm2