JD168 Series Low Differential Pressure Sensor
Application:
Power Plant Air Flow Monitor and Control Clean Room and Fume Hood Control Duct Static Pressure Measurement Draft Control HVAC and VAV Control Furnace air flow ControlGeneral Description:
JD168 series are low range differential pressure transducers and transmitters with NEMA 4(IP65)rated aluminum .They are very rugged and very reliable, good for many industrial applications.
The patented stainless steel sensor provides good corrosion resistance, excellent perform ance and long term stability.
Our unique production setup can also make special pressure range (e.g. - 0.5”WC to +3.5”WC) to meet special applications.
Features:
Up to 15 PSI Overpressure on All Ranges True Zero Output for Voltage Unit Mis-wiring Full Protection Pressure Ranges as Low as 10Pa only Unsymmetrical Bidirectional Pressure RangesTechnical Data:
Accuracy | ±1%F.S,±0.4%F.S,±0.25%F.S (BFSL) Option |
Range | ±10Pa-±10KPa, Or 0-25Pa --25KPa |
Output&Input | 4-20mA,0-5V DC,0-10V DC |
≤5.0 OHMS (Output impendence) | |
Zero Offset | <0.05%F.S/°C |
Span Offset | <0.05%F.S/°C |
Maximum Line Pressure | 15PSI(100KPa) |
External Load | 0-800 OHM |
Operating Temperature | 0 to 185°F (- 18 to 85°C) |
Excitation | 16-32VDC |
Compensated Range | 0 to 185°F (- 18 to 85°C) |
Total Error Band | ±0.75%FS(within Comp temp) |