Summarization
DALI (Digital Addressable Lighting Interface) is an international standard , popular lighting control protocol, With digital addressing dimming, stable, various dimming ways, easy to install, compatible with many big factories such characteristic.
DALI touch group control panel adopt advanced computer control chip, can group switch,dimming and programme of dimmer on bus, also can use button without computer to operate, it is convenience for user.
Technical parameters
Supply voltage: DALI bus signal
Working temperature: -20-60 °C
Storage temperature: -25-55 °C
Input signal: 4 channel physics switch signal
Output signal: standard IEC60929 DALI signal
Quiescent current: < 6MA
External dimension:L86×W86×H37mm
Gross weight: 185 g
Net weight: 215g
The module which enter the programme mode group, have 2 kinds of programme way, the selected DALI dimmer "add group" and "delete group".
Choose dimmer
To make the DALI dimmer module to join delete group, first need to make the DALI dimmer which wants to be programmed in the selected sate. Press the button less than 500ms, it will select the DALI dimmer one by one, each equipment will be selected alternate.
Selected DALI dimmer "add group"
After choose the equipment, press the button, it will hear 2 buzzer rang sound, and then release the button, it can make the selected DALI dimmer add to button represents group.
Selected DALI dimmer "delete group"
After choose the equipment, press the button, it will hear 3 buzzer rang sound, and then release the button, it can make the selected DALI dimmer remove to button represents group.
Log out group programme mode
Under the programme mode, long press the button, after hear the fourth buzzer, then release, can hear continuous three sound, that prove the dimming module have quit the programme mode already.
Set button operate represents group value
DALI touch group control panel can choose broadcast or 1-2 in 16 groups to operate, choose way as the list below:
Group Selector Position rotating switch | First input Group address | Second input Group address |
0 | Broadcast | 1 |
1 | 1 | 2 |
2 | 2 | 3 |
3…9 | 3…9 | 4…10 |
A…F | 10…15 | 11…16 |
Group dimmer touch control panel