1.CE certification
2.IEC60947-4-1 stardand
3.acceptable for OEM
1.ApplicationJRS5 thermal relay is suitable for overload protection of AC motor operated on 8-houres dutyor uninterupted duty. The overload protected AC motor with frequency 50Hz, voltage up to660V, current up to 105A. Several functions provided by these relays are: phase-failure protection,temperature compensation, ON/OFF indication and manual/automatic reset. The product con-forms to IEC60947-4-1 stardand.2. Motion Characteristic: Three-phase Balance Motion Time
No | Times of thesetting current | Motion time | Start condition | Ambienttemperature |
1 | 1.05 | >2h | Cold state | 20±5oC |
2 | 1.2 | <2h | Heat state(Following the No.1 test) |
3 | 1.5 | <4min |
4 | 7.2 | 10A | 2s < Tp≤10s | ≤63A | Cold state |
10 | 4s < Tp ≤10s | >63A |
3. Phase-losing Motion Characteristic
No | Times of the setting current | Motiontime | Start condition | Ambient temperature |
Any two phases | Another phase |
1 | 1.0 | 0.9 | >2h | Cold state | 20±5oC |
2 | 1.15 | 0 | < 2h | Heat state(Following the No.1 test) |
4. Specification
Type | Setting range(A) | Forcontactor |
JRS5-12/Z | 0.2~0.28 | S-K10S-K11S-K12S-K18S-K20S-K21 |
0.4~0.6 |
0.55~0.85 |
0.7~1.1 |
1~1.6 |
1.4~2 |
1.7~2.5 |
2~3 |
2.8~4.4 |
4~6 |
5.2~8 |
7~11 |
9~13 |
JRS5-20/F | 0.2~0.28 | S-K18S-K20S-K21S-K25S-K35 |
0.28~0.42 |
0.4~0.6 |
0.55~0.85 |
0.7~1.1 |
1~1.6 |
1.4~2 |
1.7~2.5 |
JRS5-20/F | 2~3 | S-K18S-K20S-K21S-K25S-K35 |
2.8~4.4 |
4~6 |
5.2~8 |
7~11 |
9~13 |
12~18 |
16~22 |
18~26 |
24~34 |
30~40 |
JRS5-60/F | 12~18 | S-K50S-K65S-K80S-K95 |
16~22 |
18~26 |
24~34 |
30~40 |
34~50 |
43~65 |
54~80 |
65~93 |
85~105 |