Pressure range: -0.1…0~0.01…100MPa
Overpressure: 1.5 times FS or 110MPa(min. value is valid)
Pressure type: gauge, absolute or sealed gauge
--------------------------------------------------------------------------------
Accuracy: 0.25%FS(typ.) 0.5%FS(max.)
Long-term stability: 0.2%FS/year(typ. 0.3%FS/year(max.)
Zero temp. drift: 0.03%FS/°C(≤100kPa); 0.02%FS/°C(>100kPa) FS
temp. drift: 0.03%FS/°C(≤100kPa); 0.02%FS/°C(>100kPa)
Operation temp. -30°C~80°C
Storage temp.: -40°C~120°C
--------------------------------------------------------------------------------
Power supply: 15~30VDC 15~28VDC 15~28VDC
Output signal: 4~20mADC 0~10/20mADC 0/1~5/10VDC
Transmitting: 2-wire 3-wir 3-wire
Load: ≤(U-15)/0.02Ω ≤(U-15)/0.02Ω >100k
Protection: IP65 for both cable and plug connection
Electric connection: Plug connection or 1.5m cable connection
--------------------------------------------------------------------------------
Housing: stainless steel 1Cr18Ni9Ti
Diaphragm: stainless steel 316L
O-ring: Viton Rubber
casing: NBR
Compact Pressure Transmitter with display