P1245L Pressure control can protect compressors in refrigeration and air-condition plant, and keep them from over-low pressure or over-high suction pressure. P1245L Pressure control can start and stop refrigeration compressors and fans of air condensers.
P1245L Pressure control can be used not only in fluoride refrigeration,but also in air and liquid. P1245L Pressure control are fitted with a single pole double throw (SPDT) changeover switch. The position of the switch is determined by the pressure control setting and the pressure at the connector.
Approvals of P1245L Pressure control : DnV,Det norske Veritas(Norway),CQC(China),CE (Europe).
Type and data
Symbol | Model | Low pressure | High pressure | Reset | Max. work pressure | ||||
Dualpressure | P830E | -0.05→0.6 | 0.1~0.4 | 0.5→3.0 | Fixed≤0.4 | Aut. | Aut. | 1.7 | 3.3 |
P830HME | -0.05→0.6 | 0.1~0.4 | 0.5→3.0 | Fixed≤0.4 | Aut. | Man. | 1.7 | 3.3 | |
P830HLME | -0.05→0.6 | Fixed≤0.4 | 0.5→3.0 | Fixed≤0.4 | Man. | Man. | 1.7 | 3.3 | |
P1245LE | 0.2→1.2 | 0.1~0.5 | 1.0→4.5 | Fixed≤0.6 | Aut. | Aut. | 2.5 | 4.8 | |
P1245LHME | 0.2→1.2 | 0.1~0.5 | 1.0→4.5 | Fixed≤0.6 | Aut. | Man. | 2.5 | 4.8 | |
P1245LHLME | 0.2→1.2 | Fixed≤0.2 | 1.0→4.5 | Fixed≤0.6 | Man. | Man. | 2.5 | 4.8 |
Inch size, state letter “E” after the model number.
Elctrical data
Voltage | Non-inductive current | Inductive current | |
Full load | Starting | ||
A.C.110V | 24A | 24A | 144A |
A.C.220V | 16A | 16A | 96A |
P1245L Pressure control