PMAC201 Multi-channel Branch Circuit Power Meter
PMAC201 is special designed for data center managers, engineers and operational executives who are responsible for delivering power to critical applications. With direct and excellent touchpad HMI LCD displays, this technology helps you plan and optimize the critical power infrastructure to satisfy the demands of continuous availability.Pilot PMAC201 with high accuracy and full features, suits all types of unique, multi-circuit and minimal space requirements of a high performance power distribution equipments or remote power panel.Pilot PMAC201 monitors 21, 42, or 63 branch circuits (can update to 84 or more) and set up a small system, which provide information and displayed directly on the screen. The alarming capabilities can make those potential problems be dealt in time.Pilot PMAC201 designed with both excellent hardware and software, it is easy to install and convenient to operate. Those optional modules can add more solutions for any future energy challenges and energy management.
PMAC201 Branch Circuit Power Meter with following features:ØSmall size, one unit can monitor total 65 circuits ØSaving cost, saving space ØHigh reliability ØModule design: Main module, CT module, DI module, HMI Display ModuleØIt can monitor harmonic, demand, neutral current ØCT measuring accuracy: Class 0.2% ØTwo kind of alarm methods: Voice and LED ØMemory: 128M Functions of PMAC201 Ø2 main circuits and Max. 63 branch circuits electrical parameters measuring and analysis ØDI/DO status monitoring ØTwo lever alarm information for U, I abnormal ØPower load analysis monitoring and pre-alarm ØStandard 7’’ HMI display data and schematic wiring, easy to operate ØSelect strip 1, 2 or 3 CT based on branch circuits ØEvent log: Record Max. 5000 events ØSupport RS485, MODBUS communication port. MeasurementØ2 main circuits monitoring Include: U, I, P, PF, F, kWh, Demand, Harmonic, Current unbalance ØMax. 3 strips CT, Max. 63 branch circuits monitoring Include: I, P, PF, kWh, Demand
Technical Specification
Power supply | 85~265V AC or 120~ 300VDC |
MTBF | ≥50000h |
Service life | 10 years |
Rated voltage | 220Vph-N, (optional 230V), Range: 10%-120%, Accuracy: 0.5% |
Rated current (Main circuit) | 5A, Range: 1%-120% rated, Accuracy:0.5% |
Rated current (Branch circuit) | 50A, Range:1%-100% rated, Accuracy:0.5% |
Frequency | 50Hz, Range:45-60Hz, ±0.01Hz |
Power factor | Accuracy of Main:1%, Accuracy of Branch: 2% |
Active/ Reactive energy | Accuracy of Main:1%, Accuracy of Branch: 2% |
Communication | RS485 port, support Modbus-RTU |
Baudrate | 4800, 9600, 19200bps |
Status input | Wet impulse input, 220VAC, 60%-120% rated voltage |
Relay capacity | 250Vac/5A or 30Vdc/5A |
Main Module
Metal case design, high grade EMC capability
Sampling voltage, current, ON/ OFF status of mains & branch circuits
7 Inch HMI Display Module
DI (Digital Input) Module
No need aux. contact, directly monitor branch circuit status
Each status input has a indictor light.
CT (Current Transformer) Module
Suitable to install in cabinet 600mm
CT accuracy Class 0.2 to assure accuracy
1 strip has 21 CTs
Dimension
Order information
Model | Description |
PMAC201M | PMAC201 main module |
PMAC201V | Display module |
PMAC201C | CT module (Max 3 strip, each strip with 21 CT) |
PMAC201K | Status input (Max 3 strip) |
Remark:
1. PMAC201C can monitor Max 21 outgoing circuit, PMAC201M can connect Max 3 strip PMAC201C.
2. PMAC201K can monitor 21 circuit status input. And PMAC201M can connect Max 3 strip PMAC201C.