China·ZheJiang ChangKai Electrical CO.,LTD was locate d at coastal zone of south of Zhejiang province, that is ,Beautiful Yandan mountain of scenery YueQing known as China Electric Municipality. It possesses one hundred and eighty employees in total, thirty percent of which is various of professional technician. The company has completely pass ed the ISO9001 Quality System certification and obtain ed the production license, CCC Authentication, testing certification. Right of self-supporting importing and exporting.
The company conducts management principle that the Strong's collab o ration with the strong , utilizing internal resource and absorbing external advantage to greatest degree and establishes long-period collaboration and partner relationship with Xi'an high-voltage research institution , PingGao electric and ZheJiang University, which provides technical support for new product's exploration and market enlargement . Additionally, with the advanced testing equipments, consummate after -sell service, it has been awarded as advanced departm e nt and excellent enterprise by government for many years."ChangKai" products are obtain the highly praise form various, some of them are exported to Korea , Russia , Albania , Vietnam , B urma, etc. The company will insist on the management idea of "Creative sprit, unceasing struggle, seek for outstand, regard talents”, redound upon the clients with good products and considerate service.
used circuit breakers
Technical data:
LW36-72.5 outdoor high voltage AC SF6 circuit breaker | |||
Name | Unit | Value | |
Rated voltage | kV | 72.5 | |
Rated power frequency withstand voltage(1min) | To earth | kV | K·160 |
Between interrupter | K·200 | ||
Rated thunder impulse withstand voltage | To earth | K·350 | |
Between interrupter | K·410 | ||
Powerfrequency withstand voltage under zero gauge pressure of SF6(5min) | K·84 | ||
Rated frequency | Hz | 50 | |
Rated current | A | 3150 | |
Amplitude factor | 1.5 | ||
Rated short-circuit breaking current | KA | 31.5 | |
Rated short-circuit breaking current(peak) | KA | 80 | |
Rated short-circuit with stand current | KA | 31.5 | |
Rated peak value withstand current | 80 | ||
Rated short-circuit duration | s | 4 | |
Rated out-of-phase breaking current | KA | 8 | |
Breaking current of close-in fault | KA | 90%lk,75%lk | |
Rated line-charging breaking current | A | 10 | |
Operating sequence | O-0.3s-CO-180s-CO | ||
Resistance of the main circuit | μ Ω | ≤40 | |
Rated gauge pressure of SF6(20°C) | Mpa | 0.4 | |
Minimum functional gauge pressure(20°C) | Mpa | 0.35±0.03/0.30±0.03 | |
Annual leakage rate of SF6 | <0.5% | ||
Amount of water of SF6(V/V) | ppm | ≤150×10-6 | |
Mechanical life | times | 10000 | |
Electrical level of radio interference | μ V | ≤500 | |
Creepage distance | Between interrupter | mm | 2585 |
To earth | 2248 | ||
Weight of the SF6 | kg | 8 | |
Weight of the circuit breaker | kg | 1300 | |
note:external insulation level is changed by modified coefficient. Every 2000m of altitude, K=1.13;altitude3000m, K=1.28 |
mian technical data of structure | |||
Name | Unit | Value | |
Auxiliary circuit voltage | V | DC220 or DC110 | |
Thevoltage/current of the opening and closing coils | V/A | DC110/4;DC220/2 | |
Eenergy storage motor | Rated voltage | V | DC220,AC220/DC110,AC110 |
The range of normal working voltage | V | 85%-110% | |
Power | W | 600 | |
The energy storage time of motor | s | ≤15 | |
The loop voltage of the heater and the lamp | V | AC220 | |
Rated voltage of the auxiliary switch | V | DC220,AC220 | |
Rated current of the auxiliary switch | A | 10 | |
Contacts of the auxiliary switches | 10 normal opened contacts and 10 normal closed contacts |
Mechnical adjustment of the breaker | |||
Name | Unit | Value | |
Center distance between poles | mm | 1200 | |
Strode length of the moving contact | mm | 120+30 | |
Contact stroke length of the moving contact | mm | 25+20 | |
Length of the inter phaseoperating connecting rod | mm | 110+30 | |
Switch-off speed | m/s | 4.2-5m/s | |
Switch-on speed | m/s | 2.2-3m/s | |
Switch-off time | ms | ≤40 | |
Switch-on time | ms | ≤100 | |
Break time | ms | ≤60 | |
Switch-on/off time | ms | ≤80 | |
Switch-off/on time | ms | 300 | |
The time difference of the opening of three phases | ms | ≤2 | |
The time difference of the closing of three phases | ms | ≤3 |
Product display:
SF6 Circuit Breaker,used circuit breakers