Ads by Google
AC Input | |
Voltage | 3 pos 1x AC feeds (230VAC 1 ph ) |
Frequency | 45 to 66Hz |
Maximum Current | See Powersys datasheet |
Power Factor | >0.99 at 20% load or more |
Protection | Surge protection |
Internal fuses (L&N) | |
Disconnect above 300VAC | |
Monitoring | |
Monitoring unit | See powercenter datasheet |
Local operation | Menu driven software via |
keypads and LCD or PC (PowerSuite) | |
Remote operation | PowerSuite via modem or Monitoring |
via WebPower (WEB Interface, SNMP | |
protocol and email) | |
Alarm outputs | 6 relays |
Visual indications | Green LED – System ON |
Yellow LED – Minor alarm(s) | |
Red LED – Major alarm(s) | |
LCD – system status | |
Digital inputs | 6 (for monitoring of external equipment) |
Current | Battery current |
measurements | Rectifier current |
Alarms | Load fuse alarm |
Battery fuse alarm | |
LVD operated | |
Low output voltage alarms | |
(2 individual alarm levels) | |
High output voltage alarms | |
(2 individual alarm levels) | |
Battery capacity | |
Temperature alarm | |
Symmetry alarm | |
DC Output | |
Voltage | 48VDC |
Power | 3 pos 6W |
DC Distribution Options | |
No. of Load breakers | 3 pos Up to 10 mini MCB type (2-30A) |
No. of Battery fuses | 3 pos Up to 3 MCB type (60A) |
Programmable LVD | LVBD 125A |
Optional LVLD 80A | |
Connections | |
System is extractable from frame for easy access | |
Battery connections | Screw terminals |
Load MCB | Terminal blocks |
connections | |
Alarm connections | Terminal blocks |
Other Specifications | |
Isolation | 3.0 KVAC-input and output |
1.5 KVAC–input earth | |
0.5 KVDC – output earth | |
Operating temp. | -40 to+75°C (-40 to +167°F) |
Storage temp. | -40 to+80°C (-40 to +176°F) |
Dimensions | 482.6 x 44.5 x 388 mm (wxhxd) |
Weight | 8kg |
Applicable standards | |
Electrical safety | IEC 60950-1 |
UL 60950-1 | |
EMC | ETSI EN 300 386 V.1.3.2 (telecommunication network) |
EN 61000-6-1(immunity, light industry) | |
EN 61000-6-2(immunity, industry) | |
EN 61000-6-3(emission, light industry) | |
EN 61000-6-4(emission, industry) | |
Telcordia NEBS GR1089 CORE | |
Harmonics | EN 61000-3-2 |
Environment | ETSI EN 300 019-2 |
ETSI EN 300 132-2 |
Power System 3+1