Welcome to ECOL - Join Free - Sign In
33kv Aluminum Conductor XLPE Insulation Steel Tape Armored PVC Outer Sheath Electric Cables,Three Cores (AL/XLPE/STA/PVC)
33kv Aluminum Conductor XLPE Insulation Steel Tape Armored PVC Outer Sheath Electric Cables,Three Cores (AL/XLPE/STA/PVC)
Supplier Info
[China Supplier]
Contact Person : Ms. Zou Jessie
Tel : 0086-755-82958803
Fax : 0086-755-82958893
Product Detail
Aluminum conductor XLPE Insulation PVC bedding galvanized steel tape armored PVC outer sheathed cables three cores.

18/30(36)kv Three core aluminum conductors XLPE insulated to IEC 60502-2 steel tape armored cables. Cable Construction: 1. Aluminum conductor 2. Semiconductive conductor screen 3. XLPE insulation 4. Semiconductive Insualtion screen. 5. Copper tape screen 6. Fillers 7. Tape binder 8. Bedding 9. Galvanized steel tape armour 8. Outer sheath.

Voltage GradeKV18/30(36)KV
Nominal area of conductormm 2507095120150185240300400
Conductor diameter(MAX)mm8.49.911.61314.516.118.420.623.7
Weight of conductor(Approx)Kg/Km38154976295511771482194224393122
Insulation thickness(Nominal)mm2.52.52.52.52.52.52.62.83
Separation sheath thicknessmm1.31.41.41.51.61.61.71.82
Steel tape thickness(Nominal)mm0.50.50.50.50.50.50.50.50.8
Outersheath thickness(Nominal)mm2.42.52.72.82.933.23.43.7
Approximate overall diametermm47.050.554.558.061.565.571.577.586.0
Approximate cable weightKg/Km2750321038004250492055206630827011030
Minimum bending radius of cable(during installation)mm5606046526927367818539281028
Maximum DC resistance of conductor at 20 degreeohm/Km0.6410.4430.320.2530.2060.1640.1250.1000.0778
Approximate AC resistance of conductor at 90 degreeohm/Km0.8220.5680.4110.3250.2650.2110.1620.1300.102
Approximate reactance at 50Hertzohm/Km0.100.100.090.090.090.090.080.080.08
Approximate impedance at 50Hertzohm/Km0.830.580.420.340.280.230.180.150.13
Approximate capacitance of cableuf/Km0.340.380.430.470.510.560.610.630.65
Approx. charging current per phase at Uo=12KV and f=50HZmA/m0.380.430.490.530.580.630.690.710.74
Sustained current ratings          
1.Laid direct,ground temp.30 degree &g=1.2 degree  m/W,depth of laying=0.8m,laid in trefoil touchingA142174205236267298338387436
2.Drawn into ducts,ground temp.30 degree &g=1.2 degree  m/W,depth of laying=0.8m,laid singlyA120147178200227258298334383
3.Laid in air in trefoil touching,Ambient temp.35 degreeA156193230271304354414469543
One second short circuit current rating of conductorkA4.706.588.9311.2814.1017.3922.5628.2037.60

33kv Aluminum Conductor XLPE Insulation Steel Tape Armored PVC Outer Sheath Electric Cables,Three Cores (AL/XLPE/STA/PVC)

Ads by Google

Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.