Ads by Google
Product Instuction | |||||
Paper wrapped transposed conductor uses many varnished copper flat wires,transposed and twisted by stranding cage,and then wraps insulating paper. | |||||
Application | |||||
It's main used in the manufacture of large oil-immersed transformer, reactor and winding of large capacity dry type transformer. | |||||
Feature | |||||
Can significantly reduce eddy current loss in the process of transformer operation | |||||
reduce the weight and volume of the transformer, | |||||
good heat dissipation,low cost of transformer | |||||
good strength of extension and anti-short circuit ability | |||||
Type:paper insulation acetal transposition conductor,paper insulation hot sticky and acetal transposition conductor,paper insulation half-hard acetal transposition conductor,paper insulation half hard hot sticky and acetal transposition conductor,NOMEX insulating paper polyester imide transposition conductor,etc. | |||||
Product technical parameters | |||||
Transposition quantity | |||||
5~63nos | |||||
Maximum outside line size(Excluding lapped insulation) | |||||
80*26(mm)height-width ratio H/W≤6 | |||||
Range of single conductor dimension | |||||
A:0.90~3.55(mm)B:2.00~13.50(mm) | |||||
Transpoition pitch | |||||
general requirements: 8b~16bcalculation formula:S=Dπ/nS:transpoition pitchD:minimum diameter of coiln:transposition number of transposed conductor | |||||
lining paper | |||||
In order to improve the transposition conductor axial tensile strength,To prevent the paint film will be damaged,use a certain thickness of insulating paper as isolation layer between lines,it's named lining paper.Thickness of lining paper:0.13mm | |||||
Half hard strength provisions | |||||
Half hard copper performance index | |||||
Model | Yield strength | Minimum elongation | Maximum resistivity | ||
C1 | 100~180 | 20 | 1/58 | ||
C2 | 180~200 | 20 | 1/57.5 | ||
200~220 | 15 | 1/57.5 | |||
C3 | 220~260 | 15 | 1/57 | ||
Insulating paper | |||||
Type of insulating paper: cable paper,High density insulating paper,heat insulating paper,dannisong paper,TYVEK etc. | |||||
Insulating layer provisions | |||||
Insulation standard thickness(mm) | Allowable deviation(mm) | ||||
0.45~0.60 | ±0.06 | ||||
0.61~1.05 | ±0.08 | ||||
1.06~2.00 | ±0.10 | ||||
≥2.00 | ±0.12 | ||||
Outside line size calculation | |||||
Height:H=1/2(n+1)A+Δ | |||||
Width:W=2B+Δ | |||||
A:Thickness of single conductor | |||||
B:Width of single conductor | |||||
Δ:Thickness of insulating paper | |||||
Executive standard | |||||
OB/T 6758.1~4-2007 |