liquid level switch
• Liquid Level Switch for the detection of the liquid level in tanks and process vessels • Level switch response time of 0.1 to 1 second of wetting (media dependent)• Wide operating temperature range of -100F to +390F (-70C to 200C)• Operating Pressure: to 3000 psia (207 bar)• CE, CENELEC and CSA approval• Repeatability: +/- 1% of set point (Flow) or 1/32î (0.8mm) Level• Stability: Drift <0.5% from calibrated set point over a range of +/-50F • Temperature compensated through entire range• Enclosure: Explosion Proof; NEMA 3, 4X, 7, 9. CSA, FM, UL, CENELEC and EECS approved• Process Connection: 0.75" MNPT standard. 0.5" and larger MNPT and various other process connections such as sanitary and flanges optional• Insertion Length: 2.0" standard. 0.5" or greater optional• Input Power: 115 VAC, 50/60Hz standard. 230 VAC, 50/60Hz optional, 24VDC optional. 3.1 Watt maximum• Output: 5A. 250 VAC. DPDT with fail safe capability