Product Application
NKP-TEL-6J-1 is designed for DC signal line including 2-Wire transmitters. It absorbs the lightning surges that are transmitted in the DC signal wiring to insure the line potential will remain at components. The unit is designed not to fall in the shortcircuit condition, thus protecting the equipment from any damage caused by short circuits.
Technical information/ Product parameters
Type | NKP-TEL-6J-2 |
Application | Analog data 4~20mA,0~24V |
Nominal voltage Un | 24V |
Max. continuous operating voltage | 41V |
Normal discharge current (8/20 us) | 5 kA |
Max. discharge current(8/20 us) | 10 kA |
Voltage protection level | ≤130V |
Protected core wire | 4 line |
Response time | 1 ns |
Insert Wastage | ≤ 0.3 dB |
Nominal load current | 100 mA |
I/O connector | Terminal block |
Cross-sectional area | 0.2~2.5 mm2 |
Outer covering material | PA66 |
Dimension(mm) | 80×60×30m |
Installation | DIN 35mm |
Operating temperature range | -40°C to +80°C |
Lightning protection zone | LPZOA-2 |
Degree of protection | IP20 |
Test standards | IEC61643-21 |