NA1960 Specifications
Main functions:
1 Display voltage: display current power voltage value
2 Overload and under voltage: when power voltage is too low or too high, cut off all the equipment power, and overload and under voltage value can be set.
3 Display electric current: display average three-phase electric current, can display A,B,C three-phase’s electric current by pressing each key.
4 Overload protection: when average three-phase electric current is more than setting electric current, cut off load to protect circuit.
5 Losting-phase protection: when controller checks lacking phase or three-phase electric current doesn’t remain in equilibrium seriously , cut off load to protect circuit.
6 Phase sequence protection: when three-phase sequence is wrong, cut off power.
7 Centralized control: controller has an interfaceRS485,to be convenient for centralized control.
8 Automatic recovery function: after cutting off load, can set an auto recovery times and interval time, switch on load again after a while. If trouble still exits after switching on load again, repeat that attempt for several times, if it still doesn’t work, it will need to be recovered manually.
Main Technique Index:
Range of Voltage Display: 300~450V
Range of setting voltage: 295~445V
Range of current display: 2.5~40A
Range of setting current: 2.5~40A
Time of overload: 1~20 seconds can be adjusted
Time of wrong phase: 1~20 seconds can be adjusted
Time of losting-phase: 1~20 seconds can be adjusted
Power supply: 9V AC(primary voltage is 380V±10%)
Operation environment: Temperature -10°C~45°C, humidity ≤85%
Output contact rating: 2A/250V AC
Executive standard: Q/320585 XYK 01