Ads by Google
Fault Location Unit:
Output Voltage:0~8kV,0~16kV,0~32kV
Capacitance:0~8kV level 64μF,
0~16kV level 16μF,
0~32kVlevel 4μF.
Maximum discharging energy:2048J
Discharging period:4~30s, adjustable
Maximum test range:64km
Test accuracy:1m
Altitude:1000m or below
Environment temperature:-10~40°C
Relative humidity:70% or below (40°C)
VLF Unit (optional):
Output frequency:0.1Hz,0.05Hz,0.02Hz
Carry capacity:0.1Hz, max. 1.1µF
0.05Hz, max. 2.2µF
0.02Hz, max. 5.5µF
Accuracy:3%
Peak-to-Peak voltage error:≤3%
Voltage waveform distortion:≤5%
Audio Frequency Unit:
Output power:20W
Output voltage:200V MAX .
Transmit signals frequency:1 kHz Sinusoid
Transmit signals mode:Continuous/Intermittent
Power Supply Unit:
Exeternal power supply Power supply:AC220V ± 10%; 50 ± 1Hz
Power consumption:≥3.5 kW
Plug:PSB-16 three core power plug, 16A/250V
YAMAHA EF6600E generator Output voltage:AC220V ± 10%;50 ± 1Hz
Output Power:5 kW
Pinpointing Device:
Locating error of high impedance fault:≤0.2m
Path detection error:≤0.2m
Locating error of low impedance fault:≤ 2 m
Power:3W
Charger input voltage:220V±10% AC
Charger output voltage:12V DC
Dimension:260mm×180mm×175mm
Weight:1.5Kg
Working temperature:-10~40°C