Station Type Surge Arrester is designed and manufactured to protect electrical equipment in the power station. The varistor used in the arrester is subjected to a series of physical and electrical tests to ensure the protective ability, and the high-level housing verifies the insulating properties. The arrester is manufactured with excellent voltage-ampere characteristics and high level of reliability and durability.
Detailed Specifications of Surge Arrester:
Type | Rated Voltage, kV | MCOV, kV | Max 0.5µs Discharge Voltage, kV (1) | Max Switching Surge Protective Level at Classifying Current Levels, kV (1) | Max Discharge Voltage Using an 8/20 Current Wave, kV | |||||
1.5kA | 3kA | 5kA | 10kA | 20kA | 40kA | |||||
HDA4-172 | 172 | 140 | 438 | 336 | 347 | 363 | 379 | 405 | 439 | 488 |
HDA4-180 | 180 | 144 | 450 | 345 | 357 | 374 | 390 | 416 | 452 | 502 |
HDA4-192 | 192 | 152 | 478 | 365 | 377 | 395 | 412 | 440 | 477 | 531 |
HDA4-228 | 228 | 180 | 568 | 436 | 450 | 472 | 492 | 526 | 570 | 634 |
HDA4-258 | 258 | 209 | 659 | 526 | 522 | 547 | 570 | 609 | 661 | 735 |
All above ratings are available with porcelain housing and polymer housing.