Welcome to ECOL - Join Free - Sign In
Intellectualized dummy AC Load Bank
Intellectualized dummy AC Load Bank
Supplier Info
[China Supplier]
Contact Person : Ms. Xie Shunli
Tel : 86-29-65660086
Fax : 86-29-65660082
Product Detail
1. Load voltage: Three-phase AC400V, Single-phase AC240V 2. power: Max 100KW (Three-phase 380V), Max 30KW (Single-phase)

 Functions & Features

-Test discharge three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time, energies of generators and UPS.

-Set/adjust discharging power according to performance parameters and detection requirements

-Set discharging time, timing to automatic shut-off load, discharge off and alarm operator

-Set over/under voltage protection threshold value, it can shut off load, terminate discharging and alarm user automatically.

-Large LCD screen, friendly interface. English menu and easy operation.

-Parallel operation function to carry out multi sets load operation by RS 485 communication

-Built-in storage function, save 30 groups of test data, which can be inquired, deleted and put into SD card.

-Start/stop discharging control by Serial port, and detect data real time operation etc; The storage data can be uploaded to PC by serial port or SD card, and the upper computer’s software can analyze data and pattern and print report etc.

-Overheating and over current protection function, it can turn off load, terminate discharging and alarm automatically when over temperature and over current.

-Set at most 5 groups power, load process automatically according to the setting power and operation time after being turned on. 

Technical Parameters

Mode

ACO 380/10

Condition of Circumstance

Working Temperature: (-20~55)°C      

Storage Temperature: (-45~70)°C

Relative humidity: 90%(40±2°C)

Atmospheric pressure: (70~106)KPa

External Dimensions(mm)

650×600×900mm

Weight

70kg

Working Voltage

Single-phase AC220V±10, 50Hz

Load voltage

Three-phase AC400V, Single-phase AC240V

Operating power

Stand-alone: Max 100KW (Three-phase 380V)

         Max 30KW (Singly-phase 220V)

Parallel Operation: Sum of all stand-alones’ max power

Discharging Time

0~(19 hours and 59 minutes) Adjustable continuously

Temperature alarm & Threshold Value

75°C

Quantity of Parallel operation

1~99 sets

Recording Period

6~999 Seconds

Voltage measurement range

AC 0~450V, Display Resolution: 0.1V, Precision: ±5‰

Current measurement range

AC 0~200A, Display Resolution: 0.1A, Precision: ±1%

Frequency measurement range

40~60 Hz, Display Resolution: 0.1Hz, Precision: ±2‰

Power measurement range

0~100 KVA, Display resolution: 0.1KVA, Precision: ±1%

Temperature measurement range

-20~100°C,Display resolution: 1°C, precision:±1°C

Cooling mode

FCT(Fan control Temperature)

Communication Mode

RS232, RS485 and USB communication

Display mode

Large LCD screen with high brightness

MTTF

≥50000h