Standard | | AJR2 developed the electronic formula Soft start-Soft stop device and passed the significance test, which is up to the national standard:(GB 14048.6-1998). |
Three-Phase Source Voltage(U) | V | 208-10%...240+10%380-15%...415+10%440-15%...500+10% |
Frequency | Hz | 50 |
Nominal Current | A | 10o≠1000 totally 20 kinds of rated value |
Motor Power | KW | |
Motor rated plate voltage | V | |
Current Regulation | | The nominal current of motor In can be regulated in the range of 0.5~1.3 times of starter's rated current.The maximum starting current can be regulated in the range of 2~7 times In, within 5 times of the starter's current limitation. |
Start-up Mode | | The starting current is limited in 5InSetting before factory leaving: when torque integral are 16 seconds, to the standard load, the current is 3In; when torque integral are 15 seconds, to the heavy load, the current is 3.5 In. |
Stop Mode | Free stop | 4 seconds, soft stop |
| Soft stop | In the range of 0.5~60 seconds, can be adjusted by programming |
| Braking stop | In the range of 0.5~60 seconds, can be adjusted by programming (Order Agreement) |
Display and Keyboard | | When operating normally, the working current (or the current percentage) of electrical motor can be showed; when operating at faults, the malfunction contents will be displayed.Keyboard are available for parameter setting-up and points setting-up and lock-in. |
Output Relay (2 pieces) | | JR | J M |
Types of Contact | 1"NO"+1"NC" | 1"NO"+1"NC" |
Setting before factory leaving | Output of the relay starting | Output of the malfunctioning relay |
Maximum working power~220V VA | Starting Power: 1200Holding Power: 120 |
Minimum switching capacity A | 100mA-24V |
Nominal working current A | 0.5 Class AC-14, AC-15(240V AV)& DC-13(48VDC) |
Nominal thermocurrent A | 5 |
Maximum working voltage | ~400V |
Service life | 5×108time |
Protection | | Integrated protection to both motor and starting device |
Main power supply protection | Phase shorting protection and phase imbalance protection, displayed by output relay |
Selective Starter | | AJR2 device can be chosen according to the nominal power and load of motor. |
| Starter's power can be used for standard load and heavy load. |