Technical specifications:
Model | Parameters | T1KL | T2KL | T3KL | ||||||
Rated power | VA/W | 1000VA/800W | 2000VA/1600W | 3000VA/2400W | ||||||
AC input | Input system | Single phrase & earth ground | ||||||||
Ranged voltage | 220VAC | |||||||||
Frequency | 50Hz | |||||||||
Voltage range | 115~300VAC | |||||||||
Frequency range | 45~55Hz | |||||||||
Voltage range of bypass | 80VAC~285VAC | |||||||||
DC input | DC nominal voltage | 24VDC/48VDC/110VDC/220VDC | ||||||||
24V | Nominal current | 40.0A | 78.4A | 117.6A | ||||||
Voltage range | 20-29VDC | |||||||||
Input low voltage/protection | 20/21VDC | |||||||||
Input high voltage/protection | 29/29VDC | |||||||||
48V | Nominal current | 19.6A | 39.2A | 58.8A | ||||||
Voltage range | 40-58VDC | |||||||||
Input low voltage/ protection | 40/42V | |||||||||
Input high voltage alarm/protection | 58/58V | |||||||||
110V | Nominal current | 8.6A | 17.2A | 25.8A | ||||||
Voltage range | 90-130V | |||||||||
Input low voltage/protection | 90/95V | |||||||||
Input high voltage/protection | 130/130V | |||||||||
220V | Nominal current | 4.3A | 8.6A | 12.9A | ||||||
Voltage range | 180-260V | |||||||||
Input low voltage/protection | 180/190V | |||||||||
Input high voltage/protection | 260/260V | |||||||||
AC Output | Output system | Single phase & earth ground | ||||||||
Output voltage | 220VAC±3%(inverter output) | |||||||||
Output frequency | 50±5Hz(normal), 50Hz±1%(abnormal) | |||||||||
Dynamic voltage transient range | <5% | |||||||||
Dynamic transient restore | < 60ms | |||||||||
Waveform | Sine wave THD<3%(linear load), sine wave THD<8% (nonlinear load) | |||||||||
Output power factor | 0.8 | |||||||||
Overload capability | 105~125%≥ 60s, 126~150%≥30s, the recover point is 90% | |||||||||
Input current peak coefficient | 3:1 | |||||||||
Transfer time | 0ms | |||||||||
Panel indicator system | LED screen + LCD indicator, show the status of inverter and operation parameter | |||||||||
Communications | RS232(turn to 485), stem node | |||||||||
Alarm function | AC/DC input under abnormal, overload condition and inverter problems | |||||||||
Protection function | AC input or output above or below the range of voltage Overload, over temperature and short circuit protection | |||||||||
Conduction | Satisfy YD/T983-1998A | |||||||||
Radiation | Satisfy YD/T983-1998A | |||||||||
Noise immunity | Satisfy YD/T983-1998A | |||||||||
Insulating resistance | > 2MΩ(500VDC) | |||||||||
Insulating strength | 2121VDC(AC input, output to ground, DC input to AC output, without flashover in one minute) | |||||||||
Cooling system | Wind cooling | |||||||||
Frequency | <55dB(1M) | |||||||||
Working environment | Temperature | -10'C~+40'C | ||||||||
Humidity | 0~95%, no condensation | |||||||||
Altitude | ≤1500M, satisfy GB3859.2-93 | |||||||||
Storage environment | Inverter temperature | -40'C~+65'C | ||||||||
Humidity | 0~95%, no condensation | |||||||||
Dimensions(W×D×H)(mm) | 438×380×83 |