Ads by Google
Model and Technical Data
Inverter Model | SolarOcean 100TL | SolarOcean 100 |
Input | ||
Max. DC Power [KW] | 115 | 115 |
Max. DC Voltage [V] | 880/1000(opt.) | 880/1000(opt.) |
Max. Input Current [A] | 250 | 250 |
MPP Voltage Range (Full Load) [V] | 450-820 | 450-820 |
Numbers of MPPT | 1 | 1 |
Strings per MPPT | 2 | 2 |
Output | ||
Rated AC Power [KVA] | 100 | 100 |
Max. AC Power [KW] | 110 | 110 |
Max. AC Current [A] | 235 | 160 |
Rated AC Voltage / Range [V] | 270/243–297 | 400/360–440 |
Rated AC Frequency / Range [Hz] | 50/45~55 | 50/45~55 |
Power Factor (cos φ) | 0.9lagging…0.9leading | 0.9lagging…0.9leading |
THDi (at rated power) | <3% | <3% |
Efficiency | ||
Max. Efficiency | 98.0% | 97.1% |
Euro Efficiency | 97.7% | 96.3% |
MPPT Efficiency | 99.9% | 99.9% |
Protection | ||
Input disconnection device | DC breaker | DC breaker |
Output disconnection device | AC breaker | AC breaker |
DC overvoltage protection /AC overvoltage protection | Class Ⅱ | Class Ⅱ |
Grid monitoring | Yes | Yes |
Ground fault monitoring | Optional | Optional |
Insulation monitoring | Optional | Optional |
Surge arrester for auxiliary supply | Yes | Yes |
Protection class (as per IEC 62103) /overvoltage category (as per IEC 60664-1) | ClassⅠ/Ⅱ | ClassⅠ/Ⅱ |
General Data | ||
Topology | Transfomerless | Transfomerless |
Dimension(W*H*D)[mm/in] | 1160 *1970*900/45.7*77.6*35.4 | 1160 *1970*900/45.7*77.6*35.4 |
Weight [kg/lb] | 530 /1168 | 935/2061 |
Operating Temperature Range [°C/°F] | -30~+55/-4~122 | -30~+55/-4~122 |
External auxiliary supply voltage | 230/400V(L-N-PE/L-L-PE) | 230/400V(L-N-PE/L-L-PE) |
Cooling | Fan | Fan |
Ingress protection(IP) | IP20 | IP20 |
Humidity (non-condensing) | 5%~95% | 5%~95% |
Altitude | 3000m | 3000m |
Display | Touch Screen | Touch Screen |
Communication | RS485/CAN(Standard);Ethernet(Optional) | RS485/CAN(Standard);Ethernet(Optional) |
Warranty (5/10/15/20/25years) | Sta./opt./opt./opt./opt./opt. | Sta./opt./opt./opt./opt./opt. |
Certificates | 2006/95/EC, CNCA / CTS-0006-2010 (CQC)(Idt IEC 62109-1:2010, EN 61000-6-1/2/3/4, 2004/108/EC ,EN 50178 / IEC62109-1 / -2, EN 61000-3-2 / -3, IEC62116, IEC 61727, EN 50160,EN 50178 / IEC62109-1, ENEL2010, RD1663 (2000) , IEC62109-1, Refer to VDE0126-1-1 |