Ads by Google
The performance of the ceramic insulator as follows:
ceramic anti-fog type insulator
Type | U120BP | |
Unit spacing | 146mm | |
Normial diameter | 280mm | |
Norminal creepage distance | 450mm | |
Rated E&M failing load | 120Kn | |
Routine tensile load | 60Kn | |
Coupling size | 16A/16B | |
Impace strength | 10N.m | |
Power frequency withstand voltage | wet | 45Kv |
dry | 80Kv | |
Dry lightning impulse withstand voltage | 120Kv | |
power frequency pumcture voltage | 120Kv | |
Radio interferencne volltage | Test voltage to ground | 10Kv |
Max.RIV at 1MHz | 50 | |
Mass per 100pcs | 760Kg | |
Applicable standard | GB,IEC,AS,BS |