VRV Air Conditioning Equipments
Heat pump systems 10hp (28.0kW)
FDC280KXE6Q•The KX6 heat pump 2-pipe systems offer high performance VRF forapplications that require either cooling only or heating only, idealfor open plan areas.•Connect up to 16 indoor units/up to 130% capacity.•KX6 employs DC inverter compressors ONLY.•Industry leading total piping length up to 1000m and a maximumpipe run of 160m.
Item | Model | FDC255KXE6Q | FDC280KXE6G | FDC335KXE6G | FDC335KXE6Q-K | FDC400KXE6Q | FDC450KXE6Q | ||||
Horsepower rated |
| 8HP | 10HP | 12HP | 12HP | 14HP | 16HP | ||||
Power |
| three-phase 380V,50Hz | |||||||||
Rated capacity | Cooling | KW | 25.5 | 28.0 | 33.5 | 33.5 | 40.0 | 45.0 | |||
Heating | 28.0 | 31.5 | 37.5 | 37.5 | 45.0 | 50.0 | |||||
electrical characteristics | Starting current | A | 5 | 5 | |||||||
Power consumption | Cooling | KW | 6.98 | 8.09 | 9.82 | 8.94 | 11.27 | 12.97 | |||
Heating | 7.04 | 8.21 | 10.12 | 8.93 | 11.73 | 13.1 | |||||
Operating current | Cooling | A | 9.3 | 13.22 | 15.87 | 14.5 | 18.4 | 21.1 | |||
Heating | 9.9 | 13.41 | 16.36 | 14.8 | 19.6 | 21.7 | |||||
Shape dimension High x width x deep | mm | 1675×1080×480 | 1690×1350×720 | ||||||||
Net weight | kg | 218 | 221 | 224 | 317 | ||||||
Refrigerant filling quantity | R410A | kg | 11.5 | ||||||||
Operating noise | Cooling/heating | dB(A) | 55/59 | 59/60 | 61/61 | 59/59 | 59.5/60 | 62.5/62.5 | |||
Refrigerant pipe size | Liquid pipe | Mm (in) | ¢9.52(3/8") | ¢12.7(1/2") | |||||||
Trachea | ¢19.05 (7/8") | ¢22.22 (7/8") | ¢25.4(1") | ¢28.58 (11/8") | |||||||
Connection capacity | % | 50-150 | 50-200 | ||||||||
Can connect the indoor machine number |
| 15 | 19 | 22 | 22 | 36 | 40 |