PRODUCT INTRODUCTION
1) This series product can be widely deployed for enclosed area climate control such
like wireless communication cabinet, battery cabinet, Industry control cabinet etc.
2) The internal and external interface of product is IP 55 level protected to avoid
moisture, dust, water penetrating Into Inside of enclosure. Inside electronics
equipment Is completely well protected.
3) Applicable for severe ambient environment, such like high temperature, high
humidity, high corrosion atmosphere.
PRODUCT MODEL
product model | ||||||
Items | Unit | Description | HRUC A 005 | HRUC A 008 | HRUC A 010 | HRUC A 015 |
Cooling Capacity | W/ | L35/L35@50Hz | 500/1700 | 800/2700 | 1000/3400 | 1500/5100 |
Btu/h | L35/L35@60Hz | NA | NA | 1130/3850 | 1650/5600 | |
Heater | W | Optiona | 300,500 | 5,008,001,000 | ||
Air Flow | m3/h | Internal air flow | 310 | 440 | 450 | 450 |
Temp. | ºc | Operating range | -40 → +55 | |||
Noise | dB(A) | 5 m, away | 60 | 60 | 61 | 61 |
Refrigerant | R134a | |||||
Dimension | mm | W×D×H | 440*165*900 | 470*165*1170 | ||
Weight | Kg | Net Weight | 27 | 32 | 38 | 38 |
Power consumption | W | L35/L35@230V/50Hz | 360 | 500 | 540 | 570 |
L35/L35@230V/60Hz | NA | NA | 650 | 670 | ||
Voltage | V | Rated | 230V±15% | 230V±15% | 230V±15% | 230V±15% |
Frequency | Hz | Rated | 50 | 50 | 50/60 | 50/60 |
Less dehumidifying comparing traditional aircon.Environmental friendly refrigerant such like R134AHeat pressure smart control function to enable active cooling works In winter seasonCompletely safety protected accordingly UL, EN, CCC normsAlarming output to monitoring systemInterchangeable and visual display service adapterAutomatic self start after power recoveryRemote control through RS485 comm. PortProper design for easily installation and serviceSide/door mountingIntelligent self testing functionApplicable for T3 condition
How to select right cooling capacity
Firstly below calculation need to be done before hand.
Q = Qi + Qr // Q: the total heat load of enclosure.
// Qi: equipment heat load,
// Qr: heat load penetrated through surrounding wall.
Qr = K (heat transfer coefficient) * A ( surrounding wall surface area) * Δ T ( Inside cabinet temp. - ambient temp.)
So the AirCon cooling capacity = 1.1 ( capacity margin factor, normally 10% more) * Q
*The Heating function selection
1. Normally heater need to have for cold area, the size of heater need to be considered per cabinet size, temp. level, site location
2. Normally the Inside temp. should be kept under 10 degree when selecting heater size
*Tips for Installation
1. When Install the product under severe condition like dusty, high temperature, please make sure the ambient temperature not
over 60 degree, and make sure clean product quarterly.
2. Make sure the external circle well ventilated, not been blocked by surrounding obstacles, make sure no air short cutting.
3. Make sure the product well mounted and attached on your enclosure, make sure sealing tight enough to avoid air leakage.
*Others
1. Tailor made design also available such like for ocean environment usage
2. Option items: Wireless connection module through GPRS, Ethernet access, MODBUS protocol communication
CONTACT
Name: Suzhou Huarui Thermal Control Technology Co.,LtdAdd: Plant A2, No.2, Tian'e Dang Road, Wuzhong District, Suzhou, Jiangsu province, P.R.of ChinaCode: 215104Tel: +86 512 66570331/66570332-818 Fax: +86 512 68792690web site: www.hauruicooling.com