SmartHeat 9X-UR1000 Series Ultrasonic Heat Meter
9X-UR1000 series is a high performance ultrasonic heat meter from SmartHeat. Its key components include integrator, flowmeter and temperature sensor pair.
9X-UR1000 series supports standard M-BUS (European standard 1434-2007 conformance) communication functions.
9X-UR1000 series offers infrared meter reading function (when using with the meter reading instruments from SmartHeat).
9X-UR1000 series is based on the advanced multi-channel ultrasonic flowmeter, and offers higher accuracy of flow measurement. It features:
l High accurate measurement
l Good low flow
l Configured as passing the central channel, and measuring symmetric and asymmetric flow state distributions
l Reproducing the real flow by double integral on flow rate and section, and minimizing the integral error by function interpolation
l Accurate time measurement technology, rapid measurement cycle and no effect of flow pulsation
l Bi-direction metering
l Big measuring range
l Nominal size of DN25 to DN15000mm
l Shorter upstream and downstream straight pipe runs required
l Dry calibration (direct calibration) technology
l No pressure loss
l Self-diagnosis and redundancy technologies
l Optional pressure transmitter and secondary meter display
Reliable sensor performance and service life of more than 10 years.
Applicable standardsThe People's Republic of China urban construction industry standard CJ128-2007 Heat Meter. Refer to EN1434-2007, Heat Meter.
National Measurement Verification Regulation of the People's Republic of China JJG 225-2001, Heat Meter
Order numbering
Meter type | Nominal size | Pressure class | Number of channels of flowmeter | Temperature sensor | Power supply | Communication | Accuracy Class |
9X-UR-HH: Heat meter, high temperature type 9X-UR-HL: Heat meter, low temperature type 9X-UR-C: Cooling meter 9X-UR-HCH: Cooling/heat meter, high temperature type 9X-UR-HCL: Cooling/heat meter, low temperature type 9X-UR-WH: Watermeter, high temperature type 9X-UR-WL: Watermeter, low temperature type
Note: Temperature range of low temperature type: 0 to 95°C
Temperature range of high temperature type: 0 to 130°C
Note: Temperature sensor and flowmeter will vary with low or high temperature types. | -DN 50 -DN 65 -DN 80 -DN 100 -DN 125 -DN 150 -DN 200 -DN 250 -DN 300 -DN 350 -DN 400
Note: On required, other nominal sizes are available. | -P1.0: Operating pressure is 1.0MPa -P1.6: Operating pressure is 1.6MPa -P2.5:Operating pressure is 2.5MPa -P4.0:Operating pressure is 4.0MPa
(On required, other pressure classes are available.) | -CH1: 1-channel -CH2: 2-channel -CH3: 3-channel -CH4: 4-channel -CH5: 5-channel Note: For DN100 and above, 3-channel is optional. For DN200 and above, 5-channel is optional. Note: For DN125 and below, single track is optional. For DN150-DN350 dual track is optional, for DN400, triple-track is optional, for DN400 and above, have special requirements need to reserve. | -PT0: None -PT1000-A-B: Pt1000 temperature sensor
The A means the type of temperature sensor: 2: 2-wire 4: 4-wire
The B means the length of temperature sensor cable: 1.5: 1.5m 3.0: 3.0m 5.0: 5.0m 10: 10m
Note: On required, other length classes are available.
| -AC220: AC 220V power supply -AC110: AC 110V power supply -DC24: DC 24V power supply | -0: None -M: w/M-BUS communication module | -1: Accuracy Class is 1. -2: Accuracy Class is 2 -0.5: Accuracy Class is 0.5 |
Ordering example:
When a user will select a meter according to the following requirements:
Meter for heating and cooling, high temperature type, nominal size of DN200, operating pressure of less than 1.6Mpa, 5-channel flowmeter, Pt1000 sensor, 4-wire, w/1.5m cable, AC 220V power supply, w/MBUS communication module, and accuracy class 2.
Order No. is: 9X-UL-HCH-DN200-P1.6-CH5-PT1000-2-1.5-AC220-M-2
Technical parameters
Measuring range of temperature: 0 to 180°C
Temperature difference: 3 to 150K
Unit of heat: GJ, MJ, KWH optional
Communication mode: infrared (National standard conformance), M-BUS, RS-485
Degree of protection: IP67
Accuracy class: Class 2/1/0.5
Medium temperature: 0 to 95°C or 0 to 130°C
Ultrasonic channels: 1, 2, 3, 4, 5
Flowmeter accuracy diagram
Pressure loss diagramNote: Testing condition of above data is 20°C of water temperature. Theoretically, the higher the water temperature is, the lower the dynamic viscosity is, and the less pressure loss is, vice versa.
Note: Testing condition of above data is 20°C of water temperature. Theoretically, the higher the water temperature is, the lower the dynamic viscosity is, and the less pressure loss is, vice versa.
Heat meter body:
Flowmeter body:
InstallationTechnical requirements1. The installation shall be performed according to the water flow direction mark on the pipe runs, and vertical installation shall ensure that the water flows from top to bottom;
2. The valves shall be provided before and after the meter, and the accessibility shall be ensured for the maintenance;
3. The straight pipe runs shall be provided before and after the meter. For the length of straight pipe runs, refer to the “Installation method”;
4. Avoid direct sunshine and high frequency radiation sources such as motor inverter;
5. Heat meter can be installed on the water supply and return pipes, but red Pt resistance must be installed on the water supply pipes;
6. For the installation of heat meter, the location where it cannot be filled with the water shall be avoided;
Installation method
Flowmeter screens
Below DN150 (Single or 2 tracks)
DN80 DN100 DN125 DN150
Above DN150
3 Tracks, 5 Tracks
Application on site