The products can be used for power,lighting or telecommunication equipment,household electric appliance,meter and instrument,etc.
Voltages U0/U:A. Uo/U is 450/750 and 300/500.
B. Long time working temperature of or below 70°C is required for all cables or wires,except Model No BV-90 that can stand temperature up to 90°C.
C. Temperature should be above 0°C when laying the cables or wires.
Model and NameType | Name | Laying Site and Requirements | Long-time Permissible Working Temperature of Conductor(°C) |
60227IEC01/05 BV BLV | Copper Conductor,PVC Insulated Wire | Fixed laid in the circumstance of indoor, conduit etc. | 70
|
Aluminium Conductor,PVC Insulated Wire | |||
60227IEC 07 BV-90 | Heat Resistant Copper Conductor,PVC Insulated Wire at 90 | Fixed laid in the circumstance of high temperature environment and can be laid indoor, conduit etc. | 90
|
BVR | Copper Conductor,PVC Insulated Flexible Wire | Fixed laid where flexibility is required. | 70 |
BLVV | Aluminium Conductor PVC Insulated and PVC Sheathed Round Wire | Fixed laid where high mechanical protection and moisture are required. They can be laid in the air or underground. | 70 |
BVVB | Copper Conductor PVC Insulated and PVC Sheathed Flat Wire | ||
BLVVB | Aluminium Conductor PVC Insulated and PVC Sheathed Flat Wire | ||
60227IEC 02 RV227 IEC 06 RV | Copper Conductor,PVC Insulated Flexible Connector | Mainly used at middle-light type movable euipments, instrument and meters, household appliances, power and lighting and the places where flexibility is required. | 70
|
60227IEC 42 RVB | Copper Conductor,PVC Insulated Flat Flexible Connector | ||
RVS | Copper Conductor,PVC Insulated Flexible Twisting Connector | ||
60227IEC52 RVV 60227IEC53 RVV | Copper Conductor PVC Insulated and PVC Sheathed Round Flexible Connector(Light and Common Type) | ||
ZR-BVV | Copper cored Flame-retarding Cable/Wire, PVC Insulated &Sheathed | Mainly used for flame-retarding or control power line where bunch-bound cables are applicable. | 70 |
ZR-BLVV | Aluminum cored Flame-retarding Cable/Wire, PVC Insulated &Sheathed |
4. Specification Size and Technical Data
60227IEC 53 (RVV) ,RVV 300/500V
Nominal Cross-section mm² | Insulation Nominal Thickness mm | Sheath Outer Diameter mm | Upper limit OfO.D mm | Max.d.c, Resistance at20°C Ωkm | Min.insula-tion Resistance At70°C MΩkm | Recomm-ended Current Capacity [A] | Product Approximate Weight Kg/km |
2×0.75 | 0.6 | 0.8 | 7.6 | 26 | 0.011 | 13 | 58 |
2×1 | 0.6 | 0.8 | 8.0 | 19.5 | 0.010 | 15 | 67 |
2×1.5 | 0.7 | 0.8 | 9.0 | 13.3 | 0.010 | 20 | 91 |
2×2.5 | 0.8 | 1 | 11.0 | 7.98 | 0.009 | 28 | 139 |
3×0.75 | 0.6 | 0.8 | 8.0 | 26 | 0.011 | 10 | 70 |
3×1 | 0.6 | 0.8 | 8.4 | 19.5 | 0.010 | 12 | 81 |
3×1.5 | 0.7 | 0.9 | 9.8 | 13.3 | 0.010 | 18 | 115 |
3×2.5 | 0.8 | 1 | 12.0 | 7.98 | 0.009 | 24 | 176 |
4×0.75 | 0.6 | 0.8 | 8.6 | 26 | 0.011 | 10 | 85 |
4×1 | 0.6 | 0.9 | 9.4 | 19.5 | 0.010 | 12 | 106 |
4×1.5 | 0.7 | 1 | 11.0 | 13.3 | 0.010 | 15 | 145 |
4×2.5 | 0.8 | 1.1 | 13.0 | 7.98 | 0.009 | 20 | 215 |
5×0.75 | 0.6 | 0.9 | 9.6 | 26 | 0.011 | 10 | 106 |
5×1 | 0.6 | 0.9 | 10.0 | 19.5 | 0.010 | 12 | 126 |
5×1.5 | 0.7 | 1.1 | 12.0 | 13.3 | 0.010 | 15 | 180 |
5×2.5 | 0.8 | 1.2 | 14.0 | 7.98 | 0.009 | 20 | 270 |
2×4 | 0.8 | 1.1 | 12.4 | 4.95 | 0.007 | 20 | 192 |
2×6 | 0.8 | 1.1 | 15.4 | 3.3 | 0.006 | 38 | 260 |
3×4 | 0.8 | 1.2 | 13.5 | 4.94 | 0.007 | 50 | 239 |
3×6 | 0.8 | 1.2 | 16.4 | 3.3 | 0.006 | 32 | 318 |
4×4 | 0.8 | 1.2 | 14.6 | 4.95 | 0.007 | 23 | 300 |
4×6 | 0.8 | 1.3 | 18.2 | 3.3 | 0.006 | 30 | 396 |
5×4 | 0.8 | 1.4 | 16.5 | 4.95 | 0.007 | 26 | 376 |
5×6 | 0.8 | 1.4 | 20.2 | 3.3 | 0.006 | 35 | 496 |
4*4mm2 H05VV-F PVC insulated flexible copper cable