Ads by Google
TYPE:XWP-70
1. Nominal creepage distance:400mm
2.Rated E&M failing load: 70KN
3.Routine tensile load:35KN
4.Wet power frequency voltage:42KV
5.Dry power frequency voltage:80KV
6.Dry lightning impulse withstand voltage:120KV
7.Power frequency puncture voltage:120KV
8.Radio interference voltage Max RIV at 1MHz:50uV
9.Applicable standard: GB IEC
70KN Anti-pollution DISC insulators