Generating Set Specification
MODEL | R-P600 |
PRIME POWER (KVA/KW) | 600/480 |
STANDBY POWER(KVA/KW) | 660/528 |
Rated voltage(V) | 400/230 |
Rated speed(rpm) | 1500 |
Rated frequency(Hz) | 50 |
Power factor | 0.8 |
Ambient temperature(°C) | 40 |
Altitude(m) | 1000 |
Connection type | 3 phase 4 wires |
ENGINE MANUFACTURER | PERKINS |
Model | 2806A-E18TAG1A |
Rated Power(kW) | 574 |
No. of cylinders & configuration | 6 vertical in-Line |
Method of operation | 4-stroke |
Speed regulation | Electric governor |
Starting system | DC 24V Electronic start |
Cooling method | Closed-circuit cooling system |
Total displacement(L) | 18.1 |
Compression ratio | 16:1 |
Bore×Stroke(mm) | 145×183 |
100% Load fuel consumption(L/h) | ≤123 |
ALTERNATOR MANUFACTURER | STAMFORD |
Number of Phase | 3 |
Connection Type | 3Phase and 4Wires |
Number of Bearing | 1 |
Power Factor | 0.8 |
Protection Grade | IP23 |
Terminal | 12 |
Winding/ Pitch | 100% Copper 2/3 Pitch |
Cooling Fan | Cast alloy aluminum |
Exciter Type | Brushless, Self-Exciting |
Insulation Class, Temperature Rise | H/H |
Telephone Influence Factor( TIF) | TIF <50 / THF<2% |
Total Harmonic TGH/THC | <1.5% at no load / <5% at load |
Voltage Regulation, Steady State | ≤±1% |
Sustained Short-Circuit Current | 300%(3 in):10s |
CONTROL SYSTEM | DSE SERIES |
600KVA diesel generator set powered by Perkins