CJX2 LC1-D AC Contactor
Application CJX2 series AC Contactor is suitable for using in the circuits the rated voltage up to 660V AC 50Hz or 60Hz, rated current up to 95A, for making & breaking, frequently starting & controlling the AC motor. Combined with the auxiliary contact block, timer delay & machine- interlocking device etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta starter. With the thermal relay, it is combined into the electromagnetic starter. The Contactor is produced according to IEC 60947-4, GB14048-4.
Standard control voltage
Voltage | 50Hz | 60Hz | 50/60Hz |
24 | B5 | B6 | B7 |
42 | D5 | D6 | D7 |
48 | E5 | E6 | E7 |
110 | F5 | F6 | F7 |
220 | M5 | M6 | M7 |
230 | P5 | - | P7 |
240 | U5 | U6 | U7 |
380 | Q5 | Q6 | Q7 |
400 | V5 | - | V7 |
415 | N5 | - | N7 |
440 | R5 | R6 | R7 |
500 | S5 | - | - |
660 | Y5 | - | - |
Specification
Type | CJX2-09 (LC1-D09) | CJX2-12 (LC1-D12) | CJX2-18 (LC1-D18) | CJX2-25 (LC1-D25) | CJX2-32 (LC1-D32) | CJX2-40 (LC1-D40) | CJX2-50 (LC1-D50) | CJX2-65 (LC1-D65) | CJX2-80 (LC1-D80) | CJX2-95 (LC1-D95) | |
Rated working current (A) | AC3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
AC4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | |
AC3 capacity of three-phase squirrel-cage motor AC3(kW) | 220/230V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 |
380/400V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | |
415V | 4 | 5.5 | 9 | 11 | 15 | 22 | 25 | 37 | 45 | 45 | |
440V | 4 | 5.5 | 9 | 11 | 15 | 22 | 30 | 37 | 45 | 45 | |
500V | 5.5 | 7.5 | 10 | 15 | 18.5 | 22 | 30 | 37 | 55 | 55 | |
660/690V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 33 | 37 | 45 | 45 | |
Rated heat current (A) | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 125 | 125 | |
Electrical life | AC4X104 | 20 | 20-15 | 20-7 | 15-7 | 15-7 | 10-7 | 7 | 7-6 | 7-5 | 7-5 |
AC3X106 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 1.6 | 1.6 | 1.6 | |
Mechanical lifeX106 | 20 | 20 | 20 | 20 | 20 | 20 | 50 | 20 | 10 | 10 | |
Number of the contact | 3P+NO | ||||||||||
3P+NC | |||||||||||
Matched auxiliary contact type | LA1-DN02(2NC),LA1-DN11(1NO+NC),LA1-DN20(2NO),LA1-DN22(2NO+2NC),LA1-DN40(4NO,LA1-DN04(4NC),LA1-DN13(1NO+3NC),LA1-DN31(3NO+1NC) | ||||||||||
Matched time delay auxiliary contact type | Time delay after power on:LA2-DT0(0.1-3S),LA2-DT2(0.1-30S),LA2-DT4(10-180S),Time delay after power off:LA3-DR0(0.1-3S),LA3-DR2(0.1-30S),LA3-DR4(10-180S) |
AC contactor