Ads by Google
project | unit | zw32-12/T400-12.5 | zw32-12/T630-16 | zw32-12/T630-20 | |
rated voltage | KV | 12 | |||
rated current | A | 400 | 630 | 630 | |
rated short open current | KA | 12.5 | 16 | 20 | |
rated short making current(peak) | 31.5 | 40 | 50 | ||
rated peak withstand current | 31.5 | 40 | 50 | ||
rated short withstand current | 12.5 | 16 | 20 | ||
rated short duration | s | 4 | |||
rated isolation level | thunder impulse withstand voltage (peak ) | kv | alternated, to earth75, fracture85 | ||
1min power frequency withstand voltage | alternatedto earth 42 tracture85 | ||||
rated operating sequence | close-0.3s- open and close-180s- open and closeelectromotion agency | ||||
operations of short-circuit making current breaking current interruption | 30 | ||||
mechanical life | 10000 | ||||
rated operating voltage(open and close coil) | v | DC220 110 AC220 110 | |||
contact erosion permission length | mm | 3 | |||
rated current of overcurrent trip | A | 5 | |||
current ratio of mutual inductor | 200/5 400/5 600/5 | ||||
rated contact stroke | mm | 9±1 | |||
2±0.5 | |||||
average opening speed | m/s | 1.2±0.3 | |||
average closing speed | 0.6±0.2 |
ZW32-12 Outdoor Vacuum Circuit Breaker