1.About us
We're specialized in designing and manufacturing contactor and circuit breaker in China with the experience of more than 15 years and with the export experience of more than 10 years,manufacturing according to the ISO9001 quality control system guidelines and IEC and EU standard. We help our customers develop the specical products as per their inquiries and OEM service offered.
2.About the product
1).The product is mainly used in circuit with AC 50/ 60Hz, voltage 230V up to 400V, current 1A up to 63A for protecting cables and equipment against overload and short circuit.and also for isolation.
2).The product adopts advanced technologies and the latest materials to improve its breaking capacity and electrical life.
3).Highly standard modular design is to reduce variety of parts and improve its reliability.
4).The feature is compact constructure ,small volume,light weight ,advanced current-limit technology,high breaking capacity and convenient mounting and so on.
5). The main components(expect those easily disable parts) can last as long as up to more than 30,000 hours.
6).Products and all key components are finished by precisely machining and accurately assembling, and strictly tested and therefore high quality is reached.
3.Main technical data
Rated current In | A | 1,2,3,4,6,10,16,20,25,32,40,50,63 | ||
Electrical features | Poles | 1P,2P,3P,4P | ||
Rated voltage Ue | V | 230/400 | ||
Insulation voltage Ui | V | 500 | ||
Rated frequency | 50/60Hz | |||
Rated breaking capacity | A | 10000 | ||
Energy limiting class | 3 | |||
Rated impulse withstand voltage (1.2/50)Uimp | V | 6000 | ||
Dielectric test voltage at ind .Freq.for 1min | kV | 2 | ||
Pollution degree 2 | ||||
Power loss per pole | Rated current(A) | Max power loss per pole (W) | ||
1,2,3,4,6,10 | 2 | |||
16,20,25,32 | 3.5 | |||
40,50,63 | 5 | |||
Thermo-magnetic release Characteristic | B,C,D | |||
Mechanical features | Electrical life 8000 | |||
Mechanical life 20000 | ||||
Contact position indicator Yes | ||||
Protection degree IP40 | ||||
Reference temperature for Setting of thermal element | °C | 30 | ||
Ambient temperature (with daily average≤35°C) | °C | -5…..+40 | ||
Storage temperature | °C | -25….+70 | ||
Installation | Terminal connection type | Cable /U-type busbar/pin-type busbar | ||
Terminal size top/bottom for cable | mm2 | 25 | ||
AWG | 18-3 | |||
Terminal size top/bottom for busbar | mm2 | 25 | ||
AWG | 18-3 | |||
Tightening torque | N*m In-Ibs | 2.0 22 | ||
Mounting | On DIN rail 35mm | |||
Connection | From top and bottom | |||
Combination with occessories | Auxiliary contact | Yes | ||
Shunt release | Yes | |||
Under voltage release | Yes | |||
Alarm contact | Yes |
4.Overcurrent protection characteristics
Serial No. | Initial status | Setting current | Conventional time | Expected results | Release type |
a | Cold status | 1.13In | t≥1h | Non-tripping | B,C,D |
b | Right after test no.a | 1.45In | t<1h | Tripping | B,C,D |
c | Cold status | 2.55In | 1s<t<60s(In≤32A) | Tripping | B,C,D |
1s<t<120s(In≤32A) | |||||
d | Cold status | 3In | t≥0.1s | Non-tripping | B |
5In | C | ||||
10In | D | ||||
e | Cold status | 5In | t<0.1s | Non-tripping | B |
10In | C | ||||
16In | D |
5.Thrmo-magnetic release characteristic curves
6.Overall ad mounting dimension(mm)
7.Package pictures
( function(){ var aBigImageSrc = [ 'http://i01.i.aliimg.com/photo/v18/555408493_1/SB2_L7_2p_10ka_breaking_capacity_mini.jpg' , 'http://i01.i.aliimg.com/photo/v18/555408493_2/SB2_L7_2p_10ka_breaking_capacity_mini.jpg' ]; var oProductShow = new AE.run.minisite.productShow(); oProductShow.init( { 'aImgSrc': aBigImageSrc } ); } )(); SB2 ( L7 ) 2p 10ka breaking capacity mini circuit breaker with short circuit and overload protection