Product Detail
1.components made by plastic and copper 2.meet EU standard 3.size W*L*H=35*80*60 4.short circuit and overload protection .

1.About us

   We're specialized in designing and  manufacturing contactor and circuit breaker in China with the  experience  of more than 15 years and with the export experience of more than 10 years,manufacturing according to the ISO9001 quality control system guidelines and IEC and EU standard. We help our customers develop the specical products as per their inquiries and OEM service offered.

2.About the product

   1).The  product   is mainly used in circuit with AC 50/ 60Hz, voltage 230V up to 400V, current 1A up to 63A  for protecting cables and  equipment against overload and short circuit.and also for isolation.

   2).The product adopts advanced technologies and the latest materials  to improve its breaking capacity and electrical life.

   3).Highly standard modular design is to reduce variety of parts and improve its reliability.

   4).The feature is compact constructure ,small volume,light weight ,advanced current-limit technology,high breaking capacity and convenient mounting and so on.

   5).  The main components(expect those easily disable parts) can last as long as up to more than 30,000 hours.

   6).Products and all key components are finished by precisely machining and accurately assembling, and strictly tested and therefore high quality is reached.

3.Main technical data

Rated current In

A

1,2,3,4,6,10,16,20,25,32,40,50,63

Electrical

features

Poles

1P,2P,3P,4P

Rated voltage Ue

V

230/400

Insulation voltage Ui

V

500

Rated frequency

50/60Hz

Rated breaking capacity

A

10000

Energy limiting class

3

Rated impulse withstand

voltage (1.2/50)Uimp

V

6000

Dielectric test voltage at

ind .Freq.for 1min

kV

2

Pollution degree                       2

Power loss per pole

           Rated current(A)

Max power loss per pole (W)

             1,2,3,4,6,10

2

             16,20,25,32

3.5

             40,50,63

5

Thermo-magnetic release

Characteristic

B,C,D

Mechanical

features

Electrical life                           8000                

Mechanical life                         20000

Contact position indicator                 Yes          

Protection degree                       IP40

Reference temperature for

Setting of thermal element

°C

30

Ambient temperature (with

daily average≤35°C)

°C

-5…..+40

Storage temperature

°C

-25….+70

Installation

Terminal connection type

Cable /U-type busbar/pin-type busbar

Terminal size top/bottom

for cable

mm2

25

AWG

18-3

Terminal size top/bottom for

busbar

mm2

25

AWG

18-3

Tightening torque

N*m

In-Ibs

2.0

22

Mounting

On DIN rail 35mm

Connection

From top and bottom

Combination with occessories

Auxiliary contact

Yes

Shunt release

Yes

Under voltage release

Yes

Alarm contact

Yes

   

  

4.Overcurrent protection characteristics

Serial No.

Initial status

Setting current

Conventional time

Expected results

Release type

a

Cold status

1.13In

t≥1h

Non-tripping

B,C,D

b

Right after test no.a

1.45In

t<1h

Tripping

B,C,D

c

Cold status

2.55In

1s<t<60s(In≤32A)

Tripping

B,C,D

1s<t<120s(In≤32A)

d

Cold status

3In

t≥0.1s

Non-tripping

B

5In

C

10In

D

e

Cold status

5In

t<0.1s

Non-tripping

B

10In

C

16In

D

 5.Thrmo-magnetic release characteristic curves

    

6.Overall ad mounting dimension(mm)

   

7.Package pictures

    

( function(){ var aBigImageSrc = [ 'http://i01.i.aliimg.com/photo/v18/555408493_1/SB2_L7_2p_10ka_breaking_capacity_mini.jpg' , 'http://i01.i.aliimg.com/photo/v18/555408493_2/SB2_L7_2p_10ka_breaking_capacity_mini.jpg' ]; var oProductShow = new AE.run.minisite.productShow(); oProductShow.init( { 'aImgSrc': aBigImageSrc } ); } )(); SB2 ( L7 ) 2p 10ka breaking capacity mini circuit breaker with short circuit and overload protection

Ads by Google

Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 ECOL Limited and/or its subsidiaries and licensors. All rights reserved.