Item | Unit | ZW32-12/T400-12.5 | ZW32-12/T630-16 | ZW32-12/T630-20 | |
Rated voltage | kV | 12 | |||
Rated current | A | 400 | 630 | 630 | |
Rated short-circuit break current | kA | 12.5 | 16 | 20 | |
Rated short-circuit close curren t(peak value) | 31.5 | 40 | 50 | ||
Rated peak value withstand current | 31.5 | 40 | 50 | ||
Rated short-circuit withstand current | 12.5 | 16 | 20 | ||
Rated short-circuit duration | 4 | ||||
Rated insula-tion level | Thunder impulse withstand voltage(peak value) | S | Interphase,grounding insulation75,fracture85 | ||
1min industrial frequency withstand voltage | kV | Interphase, grounding insulation42,fracture48 | |||
Rated operation order | Off-0.3S on and off-180S-on and off(electromotion framework) | ||||
Rated short-circuit current break and close time | (times) | 30 | |||
Mechanical life-span | 10000 | ||||
Rated operation voltage(on-off coil) | v | DC220, 110, AC220 | |||
Allowance abrasion cumulated thickness ofthe moving and stationary contact | mm | 3 | |||
Rated current ofovercurrent trip | A | 5 | |||
Current rate of current mutual inductor | 200/5 400/5 600/5 | ||||
Switching distance of the contact | mm | 9±1 | |||
Contact exceed degree | 2±0.5 | ||||
Average speed of breaking brake | M/s | 1.2±0.3 | |||
Average speed of closing brake | 0.6±0.2 | ||||
Time of breaking brake | ms | 3060 | |||
Time of closing brake | 2040 | ||||
Bounce time of closing brake | ≤2 | ||||
The corresponding performance of three-phase breaking & closing brake | ≤2 | ||||
Loop direct current resistance of each phase | μΩ | ≤80 | |||
Power storage electromoto | Rated voltage | V | -220 | ||
Rated power | W | 200 | |||
Power storage time | s | ≤8 | |||
Weight | kg | 85 |