Item | Unit | Data |
31.5kA | 40kA | 50kA |
Rated voltage | kV | 12/17.5/24kV |
Maximum working voltage | kV | 12 |
Rated current | A | 1250, 16002000, 2500 | 1250, 16002500, 3150 | 1250, 25003150 |
Rated short-circuit break current | kA | 31.5 | 40 | 50 |
Rated short-circuit close current(peak value) | kA | 80 | 100 | 125 |
Rated peak value withstand current | kA | 80 | 100 | 125 |
4S Rated little withstand current | kA | 31.5 | 40 | 50 |
Rated in sulation level | Industrial frequency withstand voltage | kV | 42/50/60 |
Thunder impulse withstand voltage | 75/95/125 |
Rated operation order | | -0.3S--180S-Off-0.3S on and off-180S-on and off |
Mechanical life-span | times | 10000 |
Rated short-circuit current break and close time | times | 50 |
Speak and move organization amount equal to the voltage of thefloodgate(DC) | V | 110,220 |
Speak and move organization amount assign the current of thefloodgate(DC) | V | 110,220 |
Switching distance of the contact | mm | ≥11 |
Ultra journey(touches the head springand compresslength) | mm | 4±0.5 |
three-phase breaking intoshut floodgate sex of the same period | ms | ≤2 |
Touch the head and shut a floodgate of time of bouncing | ms | ≤2 |
Average speed of breaking brake | m/s | 0.91.2 |
Average speed of closing brake | m/s | 0.60.8 |
Time of breaking brake | Operate it under the voltage highest | s | ≤0.05 |
Operate it under the voltage temostlow | ≤0.08 |
Time of closing brake | s | ≤0.1 |
Each the resistance of main return circuit | μΩ | ≤40 |
Allowance abrasion cumulated thickness of the moving andstationary contact | mm | 3 |