DescriptionThe electronic ballast WK-T8-432/IS/120HSC is a green light product, it is suitable for fluorescent lamps: F17T8,F24T8,F25T8,F25T12,F31T8,F32T8 and F40T8.Line Voltage: 120vac, ±10%, 60Hz Instant Start
UL No.: E247096
Parallel Lamp Operation
Lamps | InputWatts | LineCurrent(amps) | PowerFactor | BallastFactor | Ballast Efficacy Factor | HarmonicTotal | CrestFactor | |
Type | # | |||||||
F32T8 | 4 | 113 | 0.95 | >99% | 87% | 0.77 | <8% | <1.7 |
F31T8 | 4 | 112 | 0.94 | >99% | 87% | 0.78 | <8% | <1.7 |
F25T8 | 4 | 87 | 0.73 | >99% | 91% | 1.05 | <10% | <1.7 |
F25T12 | 4 | 93 | 0.78 | >99% | 89% | 0.96 | <10% | <1.7 |
F24T8 | 4 | 85 | 0.72 | >99% | 91% | 1.07 | <10% | <1.7 |
F17T8 | 4 | 62 | 0.52 | >98% | 92% | 1.48 | <15% | <1.7 |
F40T8 | 3 | 112 | 0.93 | >99% | 94% | 0.84 | <8% | <1.7 |
F32T8 | 3 | 92 | 0.77 | >99% | 96% | 1.04 | <9% | <1.7 |
F31T8 | 3 | 91 | 0.76 | >99% | 96% | 1.05 | <9% | <1.7 |
F25T8 | 3 | 74 | 0.61 | >99% | 97% | 1.31 | <11% | <1.7 |
F25T12 | 3 | 77 | 0.64 | >99% | 94% | 1.22 | <10% | <1.7 |
F24T8 | 3 | 73 | 0.60 | >99% | 97% | 1.33 | <11% | <1.7 |
F17T8 | 3 | 62 | 0.44 | >98% | 99% | 1.60 | <14% | <1.7 |
Performance:Inherent thermal protection Low harmonic distortionMinimum starting temp. : 0ºF(-18ºC) Ballast case must be groundedHigh power factor Install lamps with 3/4of grounded metal plane.Sound rate A Class P , Type 1 outdoorNo PCBs Open circuit voltage: 600VWARNING:Disconnect power when installing or servicing.